产品介绍

功能特点

The FW122W, FW122R, FW122CW, FW122CR are Remote LCD Annunciators UL listed according to UL 864 and ULC-S527 for Fire Alarm Systems for indoor use.

The FW122W/FW122R/FW122CW/FW122CR have a 7” color LCD display and 800×480 resolutions, 6 auxiliary function keys and 9 LED indicators making it the most intuitive fire-alarm user interface.

In total, up to 4 annunciators can be connected to the FW106/FW106C FACP via CAN bus to form a fire emergency detection and notification network system.

SPECIFICATION


Operating Voltage

24VDC(Powered by Panel Aux. output)

Standby Current

96mA

Alarm Current

160mA

Operating Temperature

32°F to 120°F (0°C to 49°C)

Operating Humidity

Up to 93% @ 90°F (32°C)

Weight

102.3 oz (2.9kg)

Color

White / Red

Location

Indoor dry


MOUNTING SPACE


The cabinet can be surface-mounted or flush-mounted. The mounting space is shown in figure 1.



(a)     Surface mounting



(b)     Flush mounting


Figure 1. Mounting space


INSTALLATION SIZE


1. Select a clean, dry, shock and vibration free surface in a protected environment.

2. Position the cabinet clear of obstructions so that the door opens freely and the controls and indicators are easily accessible.

3. Mark the locations of the two upper mounting bolts of the cabinet on the wall.

4. Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt.

5. Place the cabinet over the two top bolts and allow it to slide down over the bolts.

6. Mark, drill, and install the two bottom bolts in the cabinet.

7. Tighten all four bolts securely against the back wall of the cabinet.



Figure 2. Installation Size

WIRING



Figure 3. Connection


1. The 24VDC power comes from the auxiliary output(power limited) of FW106 FACP. Two connectors are available(one for input and the other for output) as shown in figure 3 and figure 4.

2. External network circuit (class B, power limited) can address up to 4 remote annunciators. When connecting annunciators on the external network circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. The rotary switch and jumper should be set correctly as shown in figure 5.

3. Connect the ground wire using the terminal provided.

4. An Ethernet standard plug is provided for temporary connection to a computer for panel programming.



Figure 4. 24VDC Connection



Figure 5. External Network Circuit


(N is the quantity of annunciator)